146
interface.
Step 2: Enter the parameters and tap . The parameters are set successfully.
Manual control generator (Does not support dry contact connection): This type of
generator only supports manual start and stop.
Automatic control generator (Supporting dry contact connection): This type of generator
supports automatic start and stop.
Number
Parameter
Description
1
Dry contact control
mode
Set the switch control mode and automatic control mode.
In the switch control mode, the start and stop of the
generator can be remotely controlled. In automatic
control mode, the generator automatically starts and
stops based on preset parameters. This feature only
applies to generators that support dry contact
connection.
2
No working time
Set a prohibited working time. During this period, the
generator will stop working. This feature only applies to
generators that support dry contact connection.
3
Rated power
Rated power of the generator.
4
Running time
The duration of continuous operation of a generator.
When the working time exceeds the set value, the
generator will automatically shut down. This feature only
applies to generators that support dry contact
connection.
5
Upper Voltage
Set the upper limit of operating frequency for the
generator.
6
Lower Voltage
The time mode will be on between the Start Time and
End Time. Set the upper limit of operating frequency for
the generator.
7
Upper frequency
Set the upper limit of operating frequency for the