9.6.2.2 Setting the Reactive Power Mode
Setting the Fix PF
Step 1: Tap Home > Settings > Advanced Settings > Safety Parameter Settings >
Reactive Power Mode to set the parameters.
Step 2: Set the parameter based on actual needs. The power factor remains fixed during
the inverter working process.
Enable Fix PF when it is required by local grid
standards and requirements.
Set the power factor as lagging or leading based on
actual needs and local grid standards and
requirements.
Set the power factor based on actual needs. Range: 0-
~-0.8, or +0.8~+1.
Setting the Fix Q
Step 1: Tap Home > Settings > Advanced Settings > Safety Parameter Settings >
Reactive Power Mode to set the parameters.
Step 2: Set the parameter based on actual needs. The output reactive power remains fixed
during the inverter working process.