[1] For Belgium Max. Output Power (W): GW70KHV-MT is 70000; GW80KHV-MT is 80000;
[2] For Belgium Max. Output Apparent Power (VA): GW70KHV-MT is 70000; GW80KHV-MT is 80000;
[1] For Belgium Max. Output Power (W): GW80K-MT is 80000;
[2] For Belgium Max. Output Apparent Power (VA): GW80K-MT is 80000;
Technical Data
DC Input Data
Max. PV Power (W)
Max. DC Input Voltage (V)
MPPT Range (V)
Starting Voltage (V)
Min. Feed-in Voltage(V)
Nominal DC Input Voltage (V)
Max. Input Current (A)
Max. Short Current (A)
No. of MPP Trackers
No. of Input Strings per Tracker
AC Output Data
Nominal Output Power (W)
Max. Output Power (W) [1]
Max. Output Apparent Power (VA) [2]
Nominal Output Voltage (V)
Nominal Output Frequency (Hz)
Max. Output Current (A)
Output Power Factor
Output THDi (@Nominal Output)
Efficiency
Max. Efficiency
European Efficiency
Protection
PV String Current Monitoring
Anti-islanding Protection
Input Reverse Polarity Protection
Insulation monitoring
DC fuse
Anti-PID Function for Module
DC SPD Protection
AC SPD Protection
Residual Current Monitoring Unit
AC Over Current Protection
AC Short Protection
AC Over Voltage Protection
General Data
Ambient Temperature Range (℃)
Relative Humidity
Operating Altitude (m)
Cooling
Display
Communication
Weight (kg)
Dimension (Width * Height * Depth mm)
Protection Degree
Night Self Consumption (W)
Topology
Certifications & Standards
Grid Regulation
Safety Regulation
EMC Regulation
GW70KHV-MT
91000
1100
200~1000
200
210
750
33/33/33/33
41.5/41.5/41.5/41.5
4
3/3/3/3
70000
77000
77000
500, 3L/PE
50/60
89
99.0%
98.4%
LCD or WiFi+APP
60
586*788*264
GW80KHV-MT
120000
1100
200~1000
200
210
800
44/44/44/44
55/55/55/55
4
3/3/3/3
80000
88000
88000
500, 3L/PE
50/60
94.1
99.0%
98.4%
LED, WiFi+APP
65
586*788*267
~1 (Adjustable from 0.8 leading to 0.8 lagging)
<3%
Integrated
Integrated
Integrated
Integrated
Integrated
Optional
Integrated(Type II)
Integrated(Type II)
Integrated
Integrated
Integrated
Integrated
-30~60
0~100%
≤4000
Fan Cooling
IP65
<1
Transformerless
Visit homepage to achieve information.
RS485 or WiFi or PLC
Technical Data
DC Input Data
Max. PV Power (W)
Max. DC Input Voltage (V)
MPPT Range (V)
Starting Voltage (V)
Nominal DC Input Voltage (V)
Max. Input Current (A)
Max. Short Current (A)
No. of MPP Trackers
No. of Input Strings per Tracker
AC Output Data
Nominal Output Power (W)
Max. Output Power (W) [1]
Max. Output Apparent Power (VA) [2]
Nominal Output Voltage (V)
Nominal Output Frequency (Hz)
Max. Output Current (A)
Output Power Factor
Output THDi (@Nominal Output)
Efficiency
Max. Efficiency
European Efficiency
Protection
PV String Current Monitoring
Anti-islanding Protection
Input Reverse Polarity Protection
Insulation monitoring
DC fuse
Anti-PID Function for Module
DC SPD Protection
AC SPD Protection
Residual Current Monitoring Unit
Humidity Monitoring
AC Over Current Protection
AC Short Protection
AC Over Voltage Protection
General Data
Ambient Temperature Range (℃)
Relative Humidity
Operating Altitude (m)
Cooling
Display
Communication
Weight (kg)
Dimension (Width * Height *Depth mm)
Protection Degree
Night Self Consumption (W)
Topology
Certifications & Standards
Grid Regulation
Safety Regulation
EMC Regulation
GW80K-MT
120000
1100
200~1000
200
620
44/44/44/44
55/55/55/55
4
4/4/4/4 (Standard)
3/3/3/3 (Optional,
Support bifacial module)
80000
88000
88000
400, default 3L+N+PE,
3L+PE optional in settings
50/60
133
GW75K-MT
112500
1100
200~1000
200
600
44/44/44/44
55/55/55/55
4
4/4/4/4 (Standard)
3/3/3/3 (Optional,
Support bifacial module)
75000
75000
75000
380/415
50/60
133
~1 (Adjustable from 0.8 leading to 0.8 lagging)
<3%
98.8%
98.3%
Integrated
Integrated
Integrated
Integrated
Integrated
Optional
Integrated(Type II)
Integrated(Type II)
Integrated
Invegrated
Integrated
Integrated
Integrated
-30~60
0~100%
≤4000
Fan Cooling
LED, WiFi+APP
RS485 & Wi-Fi, PLC(Optional)
70
586*788*267
IP65
<1
Transformerless
Visit homepage to achieve information.
35 36