What to do if my Goodwe Inverter shows a System Failure?
- MMatthew FrankNov 18, 2025
If your Goodwe Inverter displays a system failure, it could be due to several reasons: * **Isolation Failure:** Check the impedance between Ground and PV (+) & PV (-). The impedance value must be greater than 100 kΩ. Also, ensure the inverter is properly earthed. * **Ground I Failure:** This indicates a high ground current. Unplug the inputs from the PV generator and inspect the AC system. After resolving the issue, reconnect the PV panel and monitor the inverter's status. * **Vac Failure:** The inverter will automatically restart within 5 minutes if the grid returns to normal. Verify that the grid voltage meets the specified requirements and that the neutral (N) and PE wires are securely connected. * **Fac Failure:** This indicates that the grid is not connected. Check the grid c...