74 Gossen Metrawatt GmbH
16 Special Functions – EXTRA
Depending on the test instrument configuration, either the QR
code for the Internet link to the operating instructions or the mea-
suring view for the temperature measurement is displayed.
SECUTEST ST BASE(10)
QR code: Scanning the QR code allows you to download and read
the current operating instructions from
www.gossenmetrawatt.com, for example at a tablet PC.
Feature I01 (e.g. SECUTEST ST PRO and SECULIFE ST BASE(25))
In this case, the additional functions are assigned to the rotary
switch’s EXTRA position.
Select the desired measuring function.
Measurement with Temperature Sensor
Temperature measurement is conducted with either a Pt100 or a
Pt1000 temperature sensor – the sensor type is automatically
detected internally.
Schematic Diagram
Wiring Diagram
Test Procedure with Temperature Sensor
Set the rotary switch to the EXTRA position.
Select the Temperature measurement type:
Connect the temperature sensor’s plug to the V-COM sockets
at the test instrument.
Contact the device under test.
Start the test: Press the START/STOP key.
The measured values are displayed. The measured
value recording icon shown at the right appears. Each
time this key is pressed, the currently displayed mea-
sured value is saved to buffer memory.
End the test: Press the START/STOP key.
The save icon appears (floppy disk showing the num-
ber of measured values stored to buffer memory) and
prompts you to save the measured values to a test ob-
ject ID number.
Press the ESC key in order to discard the measured
values stored to buffer memory and acknowledge by
pressing the key shown at the right.
Single Measurements, Rotary Switch Level: Green
Rotary Switch
Position
Measuring Functions Meas. Type
EXTRA None None
Single Measurements, Rotary Switch Level: Green
Rotary Switch
Position
Measuring Functions Meas. Type
EXTRA Temperature V-COM
Current clamp V-COM
EXTRA
EXTRA
EXTRA

Table of Contents

Other manuals for Gossen MetraWatt SECUTEST ST BASE