Appendix I Gram factory settings for AKCC550A (U/KG/FG cabinets)
Min. OFF-time
c02
0
0
0
Time delay for cut in of comp.2
c05
N/A
N/A
N/A
Defrost
Defrost method: 0=Off, 1= EL, 2= Gas
d01
EL
EL
EL
Defrost stop temperature
d02
6
6
6
Interval between defrost starts
d03
6
6
6
Max. defrost duration
d04
30
30
30
Displacement of time on cut in of defrost at start-up
d05
0
0
0
Drip off time
d06
4
4
4
Delay for fan start after defrost
d07
0
0
0
Fan start temperature
d08
-1
-1
-1
Fan cutin during defrost
0: Stopped
1: Running
2: Running during pump down and defrost
d09
0
0
0
Defrost sensor: 0 =Stop on time, 1=S5, 2=S4, 3=Sx
(Application 1-8 and 10: both S5 and S6.
Application 9: S5 and S5B)
d10
1
1
1
Pump down delay
d16
0
0
0
Drain delay (used at hot gas defrost only)
d17
N/A
N/A
N/A
Max. aggregate refrigeration time between two defrosts
d18
0
0
0
Heat in drip tray. Time from defrosting stops to heating in
the drip tray is switched off
d20
N/A
N/A
N/A
Adaptive defrost:
0=not active, 1=monitoring only, 2=skip allowed day, 3=skip
allowed both day and night, 4=own assessment
+ all schedules
d21
0
0
0
Time delay before opening of hot gas valve
d23
N/A
N/A
N/A
Rail heat during defrost 0=off. 1=on. 2=Pulsating
d27
0
0
0
Max. duration of -d- in display
d40
30
30
30