EasyManuals Logo

Grant Vortex Pro Installation & Servicing Instructions

Grant Vortex Pro
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #38 background imageLoading...
Page #38 background image
38
Flue System and
Air Supply
Notes:
* 75 mm with protection.
** Only applies if one or both terminals are balanced flues.
B
D
D
C
C
C
E
F
H
G
M
I
J
J
B
B
D
A
EK
L
Distances measured to rim of terminal.
Clearances recommended by Grant UK
in accordance with British Standards
and Building Regulations.
1. An opening means an openable
element, such as an openable
window, or a permanent opening
such as a permanently open air
vent.
2. Notwithstanding the dimensions
given, a terminal should be at
least 300 mm from combustible
material, e.g. a window frame.
3. A way of providing protection of
combustible material would be to
fit a heat shield at least 750 mm
wide.
Figure 9-10: Clearances for Balanced flue terminals
A Below a gutter or sanitary pipework
B Horizontal from an opening, air brick or window
C Above ground or balcony level
D Below eaves or balcony
E From an internal or external corner
F From a terminal facing the terminal
G From a surface facing the terminal
H Vertical from terminals on the same wall
I Horizontal from terminals on the same wall
J Below an opening, air brick, window etc.
K From vertical sanitary pipework
L Vertical flue from a wall
M From an oil storage tank
Min. distance (mm)Terminal position
600 *
600
300
600 *
300
1200
600
1500
750 **
600
300
750
1800
NOTE
!

Table of Contents

Other manuals for Grant Vortex Pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Grant Vortex Pro and is the answer not in the manual?

Grant Vortex Pro Specifications

General IconGeneral
BrandGrant
ModelVortex Pro
CategoryBoiler
LanguageEnglish

Related product manuals