23
9.1 Air Handler Dip Switch Settings
Default
factory setting is: Low air flow setting.
"ON" side is 0, the other side is 1.
For exam
ple:
Below is the default setting of 36K: 0010 0010
24K dip swit
ch:
Low air flow setting: 0101 (HEAT) /0101 (COOL)
Mid. air flow setting: 0110 (HEAT) /0110 (COOL)
High air flow setting: 0111 (HEAT) /0111 (COOL)
36K dip switc
h:
Low air flow setting: 0010 (HEAT) /0010 (COOL)
Mid. air flow setting: 0011 (HEAT) /0011 (COOL)
High air flow setting: 0100 (HEAT) /0100 (COOL)
48K dip switc
h:
Low air flow setting: 1011 (HEAT) /1011 (COOL)
Mid. air flow setting: 1100 (HEAT) /1100 (COOL)
High air flow setting: 1101 (HEAT) /1101 (COOL)
60K dip switc
h:
Low air flow setting: 1000 (HEAT) /1000 (COOL)
Mid. air flow setting: 1001 (HEAT) /1001 (COOL)
High air flow setting: 1010 (HEAT) /1010 (COOL)

Other manuals for Gree FLEXX Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree FLEXX Series and is the answer not in the manual?

Gree FLEXX Series Specifications

General IconGeneral
TypeHeat Pump
SeriesFLEXX
SEERUp to 20
HSPFUp to 10
RefrigerantR410A
Heating Operation Range-22°F to 75°F
Cooling Operation Range5°F to 122°F
Operating Temperature Range (Heating)-22°F to 75°F
Operating Temperature Range (Cooling)5°F to 122°F
Energy Efficiency Ratio (EER)Up to 12.5
Dimensions (Outdoor Unit)Varies by model
Weight (Outdoor Unit)Varies by model
Compressor TypeInverter
Power Supply208/230V, 1Ph, 60Hz
Noise LevelAs low as 55 dB(A)

Related product manuals