(4) Temperature unit setting
Celsius (°C) or Fahrenheit (°F) is available. As shown in the Figure 10, on the parameter setting page, 
press   (MODE) to switch the option number to 04.   (UP) or   (DOWN) is provided to allow a switch 
between Celsius (°C) and Fahrenheit (°F).
(5) Fan operation at temperature set points
The fan is able to run at the set speed, low speed or stop working when the indoor ambient temperature 
reaches the specic temperature point.
As shown in  the  Figure  11  on  the  parameter setting page,  pressing   (MODE) activates a  switch  to 
the option number 05.   (UP) or   (DOWN) is provided to allow a switch between “00”, “01” and “03”, 
adjusting the fan operation.
(6) Temperature calibration
The ambient temperature is allowed to calibrated between -5°C and +5°C with a precision of 0.5°C.
As  shown  in  the  Figure  12,  on  the  parameter  setting  page,  press    (MODE)  to  switch  the  option 
number to 06.   (UP) or   (DOWN) is provided to a 0.5°C increase or decrease within -5°C~+5°C.