Vertical Exposed Fan Coil Unit
19
(4) Temperature unit setting
Celsius (°C) or Fahrenheit (°F) is available. As shown in the Figure 10, on the parameter setting page,
press (MODE) to switch the option number to 04. (UP) or (DOWN) is provided to allow a switch
between Celsius (°C) and Fahrenheit (°F).
Figure 10
(5) Fan operation at temperature set points
The fan is able to run at the set speed, low speed or stop working when the indoor ambient temperature
reaches the specic temperature point.
As shown in the Figure 11 on the parameter setting page, pressing (MODE) activates a switch to
the option number 05. (UP) or (DOWN) is provided to allow a switch between “00”, “01” and “03”,
adjusting the fan operation.
Figure 11
(6) Temperature calibration
The ambient temperature is allowed to calibrated between -5°C and +5°C with a precision of 0.5°C.
As shown in the Figure 12, on the parameter setting page, press (MODE) to switch the option
number to 06. (UP) or (DOWN) is provided to a 0.5°C increase or decrease within -5°C~+5°C.
Figure 12