Super Free Match
Service Manual
PRODUCT
17
Model Heat pump
GKH(12)BA-K3
DNA1A/I
GKH(18)BA-K3
DNA1A/I
GKH(24)BA-K3
DNA1A/I
Cooling KW 3.50 5.00 7.10
Capacity
Heating KW 3.85 5.50 8.00
Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 220~240-1-50
Motor power input kW 0.07 0.07 0.10
m3/h 680 680 1180
Air flow volume
CFM 400 400 694
Sound pressure level
(H/L)
dB(A) 37/33 37/33 39/35
Output kW 0.035 0.035 0.035
Fan motor
Running current A 0.3 0.3 0.4
Gas inch 3/8(Φ9.52mm) 1/2(Φ12.7mm) 5/8(Φ15.9mm)
Liquid inch 1/4(Φ6.35mm) 1/4(Φ6.35mm) 3/8(Φ9.52mm)
Connecting
pipe
Connection method Flare Connection Flare Connection Flare Connection
External dia. mm Φ31 Φ31 Φ31
Drain pipe
Thickness mm 3 3 3
Body
W×D×H
mm 840×840×190 840×840×190 840×840×240
Outline
dimension
Panel
W×D×H
mm 950×950×60 950×950×60 950×950×60
Body
W×D×H
mm 963×963×273 963×963×273 963×963×325
Package
dimension
Panel
W×D×H
mm 1043×1028×130 1043×1028×130 1043×1028×130
Body Net Weight/Gross weight kg 25.0/33.0 25.0/33.0 28.0/35.0
Panel Net Weight/Gross weight kg 6.5/10 6.5/10 6.5/10
20'GP 48 48 40
40' GP 128 128 108
Loading quantity
40' HQ 144 144 128
Notes:
a. The rated cooling capacity data is measured under the following work condition: Indoor Temperature is 27
DB, 19WB. Outdoor Temperature is 35DB. The rated heating capacity data is measured under the following
work condition: Indoor Temperature is 20DB. Outdoor Temperature is 7DB, 6WB.
b. The data will change with the change of products. Refer to those parameters listed on nameplate.
c. Noise was tested in semi-silenced room, so the actual noise value will be a little higher for change of ambient.