GMV5 D.C INVERTER MULTI VRF SERVICE MANUAL
159
modes or be turned on or off. The whole device cannot be started before the conflict is solved. The
commissioning software will show the following page:
Figure 1
(2) Solution of project number conflict:
1) Manual setting on the commissioning software:
Use the commissioning software to set IDUs' project numbers separately in every system or reset
projects numbers in multiple systems.
Choose Setting -> Parameter Settings, as shown in Figure 2: