GMV5 D.C INVERTER MULTI VRF SERVICE MANUAL
241
Gas/liquid separator
Precondition: No refrigerant exists in the pipeline system and the power supply has been disconnected.
Step
Diagram
Operation Procedure
1. Loosen the hooks at
the bottom of the
electric box and the
screws.
Remove the upper and lower front
panels.
Loosen the hooks at the bottom of
the electric box.
Use a screwdriver to unscrew the
electric box.
2. Remove the electric
box.
●Disconnect internal and external
connecting lines of the electric box.
●Protect the internal parts during the
disassembly.
3. Disassemble the
gas/liquid separator.
●Heat the connecting pipes of the
gas/liquid separator by acetylene
welding and then remove the pipes.
Note: Avoid nearby parts from being
burnt during welding.
4. Remove the
gas/liquid separator.
●Unscrew and remove the gas/liquid
separator.