GMV5 D.C INVERTER MULTI VRF SERVICE MANUAL
351
Refer to section ―Hardware Debug‖ to set Modbus gateway address. Make sure the address DIP
switch on the same Modbus bus is unique and ranges from 1 to 255.
Step 2: Set the number of first IDU.
According to the number range of IDUs to be processed by Modbus gateways, the first IDU should
be numbered 1 or 129. For details, refer to section 1.4.2.4 ―Hardware Debug‖.
2.1.7.4 Communication Debug Between Modbus Gateways and Gree Remote Monitoring System
After Gree Remote Monitoring system is installed, perform the following steps:
Step 1: Configure Modbus serial port.
Choose ―Start‖ -> ―Gree CAC Remote Monitoring System‖ -> ―Com Configuration‖.
The following window is displayed. Select a serial port number and click ―OK‖.
The following window is shown. Click ―OK‖ to restart the PC.