GREE DC Inverter Side Discharge VRF for North America
133
Removal operation of gas liquid separator
Remark: Before removing the gas liquid separator, please make sure that there’s no refrigerant inside the pipeline of
system and disconnect the power
Process
Photo
Operation Instruction
1.Disconnect
inlet pipe and
exit pipe of gas
liquid separator
Weld those two
connection spots on
the gas liquid
separator and then
pull out the
connection pipe
Note: During welding
process, do not let
flame burn out other
parts
2. Replace gas
liquid separator
Loose 4 screws with
screwdriver
Replace gas lliquid
separator
3. Replace
gas liquid
separator
Weld the pipe
connected with gas
liquid separator
Fix the screws at the
base of gas liquid
separator well again
Note: During welding
process, do not let
flame burn out other
parts

Table of Contents