GREE DC Inverter Side Discharge VRF for North America
132
Remival operation for eletronic expansion valve
Remark: Before removing the electronic expansion valve, please make sure that there’s no refrigerant in th pipeline of
system and the power is disconnected
Process
Photo
Operation Instruction
1. Disconnec
the electronic
expansion valve
from the
pipeline
Remove the coil of
electroc expansion
valve at first
Weld the connection
pipe for expansion
valve, and then pull
out the connection
pipe
Note
During
welding process, do
not let flame burn out
other parts
2. Take out the
electronic
expansion valve
and replace it
Take out the
electronic expansion
valve and replace it
3. Replace
electronic
expansion valve
Weld the connection
pipe of electronic
expansion valve
Inistall the coil of
electronic expansion
valve
Note
During
welding process, do
not let the flame burn
out other parts