GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
231
causes phase loss or reverse), it will report this error
Possible reason:
■The power supply connected to the unit is incorrect, phase loss or reverse happens
■Detecting circuit is abnormal
Troubleshooting:
2.2.4.134 “U4” Lack of refrigerant protection
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
Check the system high pressure and low pressure through pressure sensor. When the system high
pressure and low pressure is lower than 5 of outdoor ambient temperature before starting operation, the
unit will stop for protection.
Possible reason:
■Refrigerant charging amount is insufficient;
■System pipeline is leaked;
Troubleshooting:
2.2.4.135 “U6” Valve error
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display