Multi Variable Air Conditioners Duct Type Indoor Unit
12
Fig 4.8
4.3.2 Installation of Drain Pipe
(1) Insert the drain hose into the drain hole and tighten it with tapes, as shown in Fig 4.9
(2) Tighten the pipe clamp, with the distance between screw nut and hose smaller than 4mm.
metal clamp(accessory)
drain hose(accessory)
Grey tape(accessory)
(3) Use sealing plate to make the pipe clamp and hose insulated, as shown in Fig 4.10
metal clamp(accessory)
thermal sponge(accessory)
Fig 4.9
Unit: mm
Fig 4.10
(4) When connecting several drain pipes, follow the instruction as indicated in Fig4.11. Choose
the drain collecting pipe that matches with unit capacity.
Unit: mm
Fig 4.11
(5) For indoor units that have high pressure at the outlet of drain pipe, use water-sealed joint.
(6) For indoor units that have high pressure at the outlet of drain pipe, use water-sealed joint.
(7) Install the water-sealed joint according to Fig 4.12.