Multi Variable Air Conditioners Duct Type Indoor Unit 
24 
7 Malfunction Codes of IDU 
Error 
Content 
Error 
Content 
Error 
Content 
L0  Indoor Unit Error  L9 
Quantity Of Group Control 
Indoor Units Setting Error 
d7  Humidity Sensor Error 
L1  Indoor Fan Protection  LA 
Indoor Units Incompatibility 
d8 
Water Temperature Sensor 
L2  E-heater Protection  LH  Low Air Quality Warning  d9  Jumper Cap Error 
L3  Water Full Protection  LC 
Outdoor-Indoor 
dA 
Indoor Unit 
L4 
Wired Controller Power 
d1 
Indoor Unit Circuit Board 
dH 
Wired Controller Circuit Board 
Error 
L5  Anti-freezing Protection  d3 
Ambient Temperature 
dC 
Capacity DIP Switch Setting 
L7  No Master Indoor Unit Error  d4 
Inlet Pipe Temperature 
dL 
Outlet Air Temperature 
L8 
Power Insufficiency 
d6 
Outlet Pipe Temperature 
dE 
Indoor Unit CO
2
 Sensor 
o1  Over low voltage of IDU bus  o2 
Over high voltage of IDU 
o3  IDU IPM module protection 
o4  IDU startup failure  o5  IDU overcurrent protection  o6 
IDU current detecting circuit 
o7 
IDU non-synchronism 
o8 
IDU drive communication 
o9 
Communication error of IDU 
oA 
Over high temperature of IDU 
ob 
Temperature sensor error of 
oC  IDU charging circuit error 
o0  Other drive error  db 
Special Code:   
—  — 
8 Troubleshooting 
If your air conditioner is not working well, please check the following table first before asking for 
service: 
NOTICE: 
If air conditioner still fails to work normally after checking and handling as described above, please 
stop using it immediately and contact local service center for assistance. 
Phenomenon  Troubleshooting 
The unit can’t start 
Power supply is not connected. 
Circuit breaker tripping caused by leakage of electricity. 
Input voltage is too low. 
The unit stops after running 
for a while 
The inlet or outlet of ODU or IDU is blocked by obstacle.   
Poor cooling effect 
Too heavy heat load of room (e.g. too many people). 
Door or windows is open. 
Inlet and outlet of IDU are blocked. 
Setting temperature is too high. 
Refrigerant is insufficient (e.g. refrigerant leakage). 
Poor heating effect 
Door or window is open. 
Setting temperature is too low. 
Refrigerant is insufficient (e.g. refrigerant leakage). 
Indoor fan doesn’t start   
up during heating   
At starting, the IDU fan could not operate till the heat exchange become hot, for 
preventing delivering the cool air. 
At defrostin
g, the IDU fan stopped due to system switch to cooling mode for 
preventing delivering the cool air, and resume operating after defrosting.