Multi Variable Air Conditioners Duct Type Indoor Unit 
8 
value. 
②  If the power cord is more than 15m long, please increase properly the sectional area of power 
cord to avoid accident due to overload. 
③  Above selection requirements: Power cord size is based on BV single-core wire (2~4pc) at 
40°C ambient temperature when laying across plastic pipe. Air switch is D type and used at 
40°C. If actual installation condition varies, please lower the capacity appropriately according 
to the specifications of power cord and air switch provided by manufacturer. 
(2)  Install cut-off device near the unit. The minimum distance between each stage of cut-off 
device should be 3mm (The same for both indoor unit and outdoor unit).   
(3)  If the supply cord is damaged, it must be replaced by the manufacturer or its service agent 
or a similarly qualified person in order to avoid a hazard. 
4 Installation Instructions 
4.1 Installation of Indoor Unit 
4.1.1 Outline Dimension and Installation Spots 
Equip with a service port after lifting the unit. For the convenience of maintenance, the service 
port should be on one side of the electric box and below unit’s lower level. 
Below are  the outline dimension applicable to indoor units of GMV-ND22~72PL/B-T,  GMV-
ND22~71PLS/B1-T. 
 
Fig 4.1 
Below are dimensions of A, B, C, etc. for different models: 
Unit: mm 
 Item 
A  B  C  D  E  F 
GMV-ND22~36PL/B-T 
760  415  710  200  450  474 
GMV-ND40~63PL/B-T GMV-
1060  415  1010  200  450  474 
GMV-ND72PL/B-T 
1360  415  1310  200  450  474