4.4 Installation of Air Duct 
NOTICE: 
①  There should be insulation layer on air-out duct, air-return duct and fresh air duct to avoid 
heat loss and moisture. Adhere a nail on the air duct and then add thermal sponge with a 
layer of tin. Fasten it with a nail cover and then seal the junction with tin tapes; you can also 
use other materials that have good insulation quality. 
②  Each air-out duct and air-return duct should be fixed on a pre-made board with iron frame. 
The junction of air duct should be well-sealed in order to prevent air leakage. 
③  The design and construction of air duct should comply with national requirements. 
④  The edge of air-return duct is suggested to be more than 150mm away from the wall. Add a 
filter to the air-return opening. 
⑤  Please consider noise-damping and vibration damping for the design and construction of air 
duct. Besides, noise source must be away from people. For instance, do not have the air-
return opening installed on top of the user (offices, rest area, etc.). 
4.4.1 Installation of Air-out Duct 
(1)  Installation of Rectangular Duct 
 
Fig 4.20 
(2)  Installation of Circular Duct 
 
Fig 4.21 