Operating Temperature Range and Rated Work Conditions of the Unit
Outdoor Operating Temperature Range of the Air-conditioning Unit
Running mode
Outdoor dry-bulb temp
Cooling -10 ~48
Heating -20 ~27
Cooling and Heating -10 ~20
Note: Cooling and Heating mode includes principle-cooling mode, principle-heating mode and
heat-recovered only mode.
Rated Work Conditions of the Unit
Condition at the Indoor Side Condition at the Outdoor Side
Running
Mode
Dry-bulb
Temperature
Wet-bulb
Temperature
Dry-bulb
Temperature
Wet-bulb
Temperature
Rated
Cooling
Cooling 27 19 35 24
Rated
Heating
Heating 20 15 7 6
Cooling 27 19
Rated
Cooling and
Heating
Heating 20 15
7 6