81
Performance Parameters of the Unit
Remarks:
1. All the data of the cooling/heating capacity and the noise are measured before the unit is shipped out from
manufacturer.
2. All the parameters in the tables below are measured under the rated work condition. Such parameters in the
specifications are subject to change so the data on the nameplate shall govern.
● Performance Parameters of the Outdoor Unit
Basic Model
GMV-Pdhm224W/Na-M GMV-Pdhm280W/Na-M GMV-Pdhm335W/Na-M
Power Supply
3phase,380~415V,50HZ,4wires system
kW
22.4 28.0 33.5
Cooling
Btu/h
76,428.8 95,536.0 114,302.0
kW
25.0 31.5 37.5
Capacity
Heating
Btu/h
85,300.0 95,536.0 114,302.0
Cooling kW
5.5 7.5 9.23
Power
Input
Heating kW
5.8 7.7 9.38
Cooling W/W
4.07 3.73 3.63
COP
Heating W/W
4.31 4.09 4.00
ECOP
Cooling &
Heating
W/W 6.8 6.5
Capacity Control %
20~100 14~100 14~100
Type -
Hermetically sealed scroll type
Compressor
NO.
-
2 2 3
Air Flow Rate m
3
/min
190 232
Dimensions(H×W×D) mm 1670×930×770 1670×1340×770
Package Dimensions
(H×W×D)
mm
1850×1010×850 1850×1420×850
Net Weight kg
260 260 372
Gross Weight kg
284 284 390
Sound Pressure Level dB(A)
58 58 61
Type - R410A
Refrigerant
Charge kg
12.0 12.0 14.0
Refrigerant Oil -
Refer to the nameplate of the compressor
Liquid mm
Φ9.5 Φ9.5 Φ12.7
Suction
Gas
mm
Φ22.2 Φ22.2 Φ28.6
Piping
Connections
Discharge
Gas
mm
Φ19.1 Φ19.1 Φ19.1
Number of Max.
Connectable Indoor Unit
-
13 16 19
Ratio of the Connectable
Indoor Unit
-
50%~135%
Recommended Power
Cord
mm
2
×NO.
6.0×5 6.0×5 10.0×5