GMV5 D.C INVERTER MULTI VRF                                                                                              SERVICE MANUAL 
105 
 
 
(2) Description of Functions 
1) A2 Refrigerant recovery operation 
This  function  partially  recovers  refrigerants  in  a  faulty  module  or  IDU  pipeline  during  unit 
maintenance. The refrigerant recovery volume of each basic module is as follows: 
Maximum Refrigerant Recovery Volume 
This function falls into two modes: faulty module refrigerant recovery and IDU pipeline refrigerant 
recovery. 
Refrigerant Recovery 
Mode Code 
Refrigerant Recovery 
Mode Name 
Indoor unit pipeline 
refrigerant recovery 
This mode is selected when an IDU fails and it is required to recover 
refrigerants from the IDU pipeline. 
Basic module refrigerant 
recovery 
This mode is selected when a basic module fails and it is required to 
recover refrigerants from this basic module. 
When this function is enabled, the ODU automatically starts and recovers refrigerants to the ODU or 
IDU pipeline. 
2) A6 Unit cooling/heating function 
This function sets operation modes of the entire unit, including: 
Cooling mode, dehumidifying mode, heating mode, and air supply mode. 
(Note: The heating mode cannot work with other modes at the same time.) 
(factory settings) 
Cooling mode, dehumidifying mode, and air supply mode. 
Heating mode and air supply mode. 
(Note: The heating mode cannot work with the air supply mode at the same 
time.) 
The user or administrator can set operation modes of the ODU based on actual situations to prevent 
conflicts.   
When it is required to set different refrigerating systems to the same function mode, set the master 
system  according  to  the  above  requirements.  For  the  master  system  settings,  see  the  "Centralized 
Control Address DIP Switch (SA2_Addr-CC)" section. 
3) A7 Outdoor silent mode 
This function is used when users require lower environment noises, including nighttime automatic 
silent mode and forcible silent mode.   
For  the  nighttime  automatic  silent  mode,  the  system  automatically  judges  the  highest  daytime 
environment temperature and then starts silent operations in a certain interval to guarantee nighttime 
low-noise operations. The nighttime automatic silent mode falls into nine categories: