GMV5 D.C INVERTER MULTI VRF SERVICE MANUAL
22
refrigeration systems, or contact local Gree sales company.
If the above equation can not be satisfied, then follow the following steps.
Selection of air conditioning system: select one of the next
1). Installation of effective opening part
2). Reconfirmation of Outdoor Unit capacity and piping length
3). Reduction of the amount of refrigerant
4). Installation of 2 or more security device (alarm for gas leakage)
Change Indoor Unit type
: installation position should be over 6.6ft from the floor (Wall mounted type Cassette type)
Adoption of ventilation system
: choose ordinary ventilation system or building ventilation system
Limitation in piping work
: Prepare for earthquake and thermal stress