GMV5 D.C INVERTER MULTI VRF SERVICE MANUAL
385
2.2.5. Software
2.2.5.1 List of Parts
Used for installing Gree CAC Remote Monitoring
System on a server PC
Providing instruction on the installation of Gree CAC
Remote Monitoring System
2.2.5.2 Preliminary Check
Check the server for network interface. If it does not have network interface, replace it with one that
has network interface. The network interface will ensure normal communication between the server and
BACnet and client.
Check the adapter and check whether server is connected to a LAN. If not, connect it to the LAN so
that the client can communicate with the server.
Check whether the BACnet gateway has been successfully debugged. If not, refer to the Technical
Service Manual of BACnet Gateway to debug BACnet gateway.
Check whether the server is configured with driver that can read disks.
Check whether the server satisfies the following software configuration requirements.
Recommended
Configuration
Internet Information Service
(IIS) manager
Main frequency: 2 GHz or higher
Windows Server 2003 SP2 or later
versions, Windows 7
NOTE:
Gree CAC Remote Monitoring System supports Windows Server 2003 SP2 or later versions
and Windows 7. Windows Server 2003 SP2 is recommended because the server can better provide
users with services in Windows Server 2003 SP2 system.
2.2.5.3 Software Setup
The software needs support of some Windows components in order to run; therefore, you should
install these components first before setup. The following installation flowchart shows you the basic
installation procedure. If some of the components have been available on your PC, you can skip
corresponding steps.