Engineering Data
11(51.8)
1.290
1.250
1.202
1.152
1.102
12(53.6)
1.340
1.300
1.252
1.200
1.152
13(55.4)
1.390
1.350
1.302
1.252
1.202
14(57.2)
1.442
1.402
1.350
1.302
1.252
15(59.0)
1.490
1.450
1.400
1.350
1.302
18(64.4)
1.539
1.502
1.451
1.402
1.350
Computer of actual cooling capacity: actual cooling capacity = nominal cooling capacity x cooling
capacity correction coefficient.
Heating Capacity Correction
GRS-CQ4.0Pd/NhG-K, GRS-CQ6.0Pd/NhG-K, GRS-CQ6.0Pd/NhG-K, GRS-CQ10Pd/NhG-K,
GRS-CQ12Pd/NhG-K,GRS-CQ14Pd/NhG-K, GRS-CQ16Pd/NhG-K, GRS-CQ10Pd/NhG-M,
GRS-CQ12Pd/NhG-M, GRS-CQ14Pd/NhG-M, GRS-CQ16Pd/NhG-M
Performance Correction
Outflow
Heated
Water
(
)
Ambient Temperature
(
)
-15(5)
-10(14)
-5(23)
0(32)
5(41.0)
10(50)
15(59.0)
20(68.0)
25(77.4)
30(86)
0.81
0.91
1.00
1.10
1.18
1.26
1.35
1.41
1.45
35(95)
0.74
0.84
0.93
1.03
1.11
1.19
1.28
1.36
1.41
40(104)
0.67
0.77
0.87
0.96
1.04
1.12
1.20
1.25
1.31
45(113)
0.60
0.70
0.80
0.89
0.97
1.05
1.13
1.19
1.25
50(122)
0.53
0.63
0.73
0.82
0.90
0.98
1.06
1.11
1.18
55(131)
0.46
0.56
0.66
0.74
0.83
0.90
0.98
1.05
1.10
Computer of actual heating capacity: actual heating capacity = nominal heating capacity x heating