Unit Control 
 
minimum operating frequency. Then if it is still detected that the leaving water temperature is lower than 
the freeze protection temperature, the main unit will stop as per the shutdown frequency but the water 
pump keeps normal operation. 
When it is detected that the leaving water temperature of the plate heat exchanger is equal to or larger 
than the freeze protection withdrawing temperature, freeze protection will exit. At this point, once the 
compressor  has  stopped  for  three  minutes  and  conditions  for  startup  have  been  satisfied,  the 
compressor will run for cooling. 
2.2 Heating 
2.2.1 Control to the Compressor 
When  the  unit  is  controlled  by  the  leaving  water  temperature,  the  operating  frequency  of  the 
compressor  will  be  adjusted  by  the  temperature  difference  in  the  way  that  it  increases  as  the 
temperature difference goes up and it decreases as the temperature difference goes down. When the 
compressor reaches the minimum frequency but the temperature frequency is still quite large, the unit 
will shut down (temperature difference= actual leaving water temperature-leaving water temperature set 
point). 
2.2.2 Over-temperature Protection 
When the compressor is running and it is detected that the leaving water temperature of the auxiliary 
electric heater is higher than the over-temperature protection temperature, the compressor will lower its 
frequency to the minimal. Then if it is still detected that the leaving water temperature of the auxiliary 
electric heater is higher than the over-temperature protection temperature, all loads except the water 
pump  of  the  main unit  and  the  4-way valve  will  stop.  Over-temperature protection  will exit  until  the 
leaving water temperature of the auxiliary electric heater is lower than the over-temperature withdrawing 
temperature. After that, the unit will resume normal operation. 
2.2.3 Control to the Optional Electric Heater 
When the Optional electric heater is deactivated through the wired controller, it will never come into 
operation. When it is activated, it will run based on the outdoor temperature. 
2.3 Water Heating     
Water heating can be achieved by either the solar system or the main unit (heat pump). 
2.3.1 Water Heating by the Main Unit   
1) When the outdoor temperature is out of the operation range, the compressor will not start, and 
water heating will be done by the water tank heater. 
2) When the outdoor temperature is within the operation range, water heating will be done by the 
main unit. The output frequency of the compressor will be adjusted by the difference between the water 
tank temperature set point and the actual water tank temperature. 
3) Control to the Water Tank Electric Heater 
a. when the water tank temperature set point is lower than the maximum value of the water heating 
range of the main unit, the auxiliary electric heater of the main unit will run depending on the temperature 
difference, and the water tank keeps shut-down. 
b. when the water tank temperature set point is higher than the maximum value of the water heating 
range of the main unit but the actual water tank temperature is lower than the maximum value of the 
water heating range of the main unit, the auxiliary electric heater of the main unit will run depending on 
the temperature difference. If the actual water tank temperature is higher than the maximum value of the