Unit Control 
 
resumes operation when defrosting ends up. 
2.7 Control to the 4-way Valve 
The 4-way valve always keeps on under the cooling mode and will off after the compressor starts up 
under the heating or water heating mode. When the unit comes into defrosting, the 4-way valve will be 
on and resume the off status when defrosting ends up. For shutdown under the heating mode, the 4-way 
valve will be closed after the compressor stops. 
2.8 Control to the Water Pump 
The water pump firstly will run at the initialized speed and then adjust the speed according to the 
entering/leaving water temperature difference. When the temperature difference is large, the fan runs at 
the high speed. When the temperature difference is small, the fan runs at the low speed. 
2.9 Control the Electrostatic Expansion Valve 
There are two electrostatic expansion valves for two-stage throttling control. The opening angle of the 
first-stage electrostatic expansion valve is adjusted based on the ratio of readings of the high-pressure 
sensor, low-pressure sensor and enthalpy-adding sensor. The opening angle of the second-stage is 
adjusted based on the suction superheating degree. 
2.10 Protection Control 
(1) Compressor Low-pressure Protection 
When it is detected continuously that pressure at the low side is too low, then low-pressure protection 
will occur and this error will be displayed at the controller, all loads act as per the shutdown sequence. 
This error is unrecoverable and can be cleared unless repowered on. 
(2) High Discharge Temperature Protection 
When  it  is  detected  continuously  that  the  discharge  temperature  is  higher  than  the  recoverable 
temperature, the electrostatic expansion valve will turn to the maximum opening angle with large step 
until the discharge temperature is lower than the recoverable temperature. However, if this condition 
remains, the compressor will restrict the frequency output or lower its frequency three times. At any time, 
if  it  is  detected  that  the  discharge  temperature  is  higher  than  the  set  point  for  protection for  three 
seconds, the compressor will stop and the unit comes into high discharge temperature protection. 
  (3) Compressor Hi-pressure Protection 
In  any  case,  when  it  is  detected  that  the  high-pressure  switch  acts,  the  unit  will  come  into 
high-pressure protection three seconds later. This protection is unrecoverable. 
(4) Flow Switch Protection 
In any case, when it is detected that the flow switch of the main unit disconnects, then all loads except 
the water pump of the solar system and the auxiliary electric heater of the water tank will stop. This 
protection is unrecoverable. The unit is allowed to be restart only after this error is cleared and the unit is 
repowered on. 
(5) Communication Error 
When the indoor unit main board or drive board does not receive correctly any data from the unit main 
board, all loads will stop.