Unit Control
segment
77~95
77
4
Duration of each segment
Segment time
12~72 hours
0
12 hours
5
Temperature difference of
each segment
ΔT of segment
2~10
/
36~50
5
/
41
1
3.
When this setting is finished, by pressing ―
Start
‖ this setting will be saved and start working, and by
pressing
Stop
‖ the function will halt.
[Notes]
● This function can be activated only when the unit is turned off. When it is done with the unit keeping
On
", a window will pop up, saying ―
Please turn off the system first!
‖.
●When this function has been activated,
On/Off
‖ operation will be deactivated. By pressing On/Off , a
window will pop up, saying
Please disable the floor debug!"
.
●When ―
Floor debug
‖ has been activated; ―
Weekly timer
‖, ―
Clock Timer
‖, ―
Temp timer
‖ and ―
Preset
mode
‖ will be deactivated.
Emergen. mode
‖,
Disinfection
‖,
Holiday mode
‖,
Manual defrost
‖,
Forced mode
and
Refri.
recovery
‖ cannot be activated at the same time with ―
Floor debug
‖. If doing so, a window will pop up,
saying
Please disable the floor debug!
‖.
●Upon power failure,
Floor debug
‖ will back to ―
Off
‖ and the runtime will be zeroed.
●When ―
Floor debug
‖ has been activated, ―
T-floor debug
‖ and
Debug time
‖ can be viewed.
●When
Floor debug
has been activated and works normally; the corresponding icon will be
displayed at the upper side of the menu page.
●Before activating ―Floor debug‖, make sure
Segment time
of each segment is not zero. If so, a
window will pop up, saying
Segment time wrong!
In this case,
Floor debug
is allowed to be
activated only when
Segment time
‖ has changed.
3.2.4.11 Manual Defrost
[Operation Instructions]
At the commissioning parameter setting page, by touching
Manual defrost
‖, the control panel will
access to the corresponding setting page.
[Notes]
●This setting will not be memorized upon power failure.
●This setting can be set only when the unit has turned off. When this function has been activated, ON
operation is un-allowed.
● Defrosting will quit when the defrosting temperature goes to 20
or the defrosting duration is equal
to 10 minutes.
3.2.4.12 Force Mode
[Operation Instructions]
1. At the commissioning parameter setting page, by touching
Force mode
‖, the control panel will
access to the corresponding setting page.
2. At the
Force mode
‖ setting page, it can be set to
Force-cool
‖, ‗
Force-heat
‖, and ―
Off
‖. When it is
set to
Force-cool
or
Force-heat
‖, the control panel will directly go back to the homepage and
response to any touching operation except the ON/OFF operation, with a window popping up, saying
The force-mode is running
!‖. In this case, by touching ON/OFF, ―
Force mode
‖ will quit.
[Notes]
●This function is allowed only when the unit has just repowered and not turned on. For the unit which
once has been put into operation, this function is unavailable, alerting ―
Wrong operation!
‖.
● It will not be memorized upon power failure.