AIR COOLED SCROLL CHILLER PRODUCT
5
Heat Pump
Net Weights
Cooling Only
kg 905 985 1565
Operation Weights
Cooling Only
kg 996 1084 1722
Notes:
Nominal capacities are based on the follow conditions:
Parameter refer to the nameplate;
Water side Air side
Item
Water flow
m
3
/(h·kw)
Leaving Water
/
Dry-bull temp.
Wet-bull temp.
Cooling 7/45 35/95
Heating
0.172
45/113 7/45 6/43
4.2 Operation Range
Water side Air side
Item
Leaving Water
(℃/℉)
Temperature Difference
of Water(℃/℉)
Air on Condenser
(℃/℉)
Cooling
515/
4159
2.56/
3743
1848/
64119
Heating
4050/
104122
2.56/
3743
-1524/
575
4.3 Electric Data
Compressor Fan Motor Total
Model
Rated
Power
Supply
Qty.
MRC
each
NRC
each
Qty.
NRC
each
MRC NRC
LSQW(R)F65M/N-M 2 31 22.1 2 2.3 66.6 48.8
LSQW(R)F80M/N-M 2 38 27.2 2 2.3 80.6 59
LSQW(R)F130M/N-M
400V-
3N-
50Hz
2 54 41.4 4 3 120 94.8
Notes:
MRC: Maximum running current (A)
NRC: Nominal running current (A)