A/A DC INVERTER U-MATCH AIR CONDITIONERS PRODUCT
10
Continued:4
Indoor unit GFH60K3CI
Model
Outdoor unit GUHD60NM3CO
kW 17
Cooling
Btu/h 58000
kW 18
Nominal
Capacity
Heating
Btu/h
61400
Cooling kW 5.3
Power Input
Heating kW 5
EER/COP
W/W
3.20/3.60
Indoor Unit GFH60K3CI
Power Supply
-
220-240V-50Hz-1Ph
Heat Exchange
-
Cross Fin Coil
Type
-
Centrifugal fan
Drive
-
direct
Motor Output kW 0.33×1
Air Flow
m3/h
3150
Fan
Ext. Static Pressure Pa 50
Sound Pressure Level(H/M/L) dB(A) 54/51/48
Air Filter
-
Standard washable synthetic
Drain Piping mm Φ30×1.5
1463×385×799
Dimensions (W×H×D)
(Outline/Package)
mm
1540×400×880
Weight(Net/Gross) kg 87/98
Outdoor Unit GUHD60NM3CO
Power Supply
-
380-415V-50Hz-3Ph
Heat Exchange
-
Cross Fin Coil
Type
-
Axial fan
Motor Output kW 0.082×2
Fan
Fan Motor Speed rpm 800±20
Type
-
ROTARY
Compressor
Power Input W 4220
Type
-
R410A
Control
-
Electronic Expansion Valve
Refrigerant
Charge kg 5.5
Dimensions (W×H×D) 1085×1365×427
(Outline/Package)
mm
1140×1390×475
Weight(Net/Gross) kg 127/133
Liquid inch Φ3/8"
Gas inch Φ3/4"
Piping
Connections
Max. Length m 50
Max. Height Difference m 30