EasyManua.ls Logo

Gree U-MATCH GUHD09NK3CO

Gree U-MATCH GUHD09NK3CO
264 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
130
Open Phase
E5 is displayed on
the wired controller
Check if wire U/V/W is
connected reliably after
the power is cut off for
1 minute.
Open Phase
LD
Monitor Display
Main Board 88
Indicating Lamp
Yes
No
Record and report the
actual condition
Connect wires reliably
If the terminal wiring
of the compressor is
reliable?
Replace the main board
Yes
Make the terminal
wiring of the
compressor reliable
or replace the
damaged compressor.
No

Table of Contents

Related product manuals