GREE              Duct type Ducted Type Split Air-Conditioner Units 
106 
Troubleshooting: 
“P5” overcurent 
protection for inverter 
compressor
Compressor driver board 
is faulted
Yes
Replace the compressor driver board
.
No
Check if the UVW wires 
are well connected?
Yes
No
Replace the compressor
Check if the 
resistance value between 
different windings of compressor 
are normal (
the normal value is less than 
2 
ohm)
?If resistances of two windings are the same
; if the 
insulation atainst ground of different windings of 
compressor are normal 
(the normal 
value is less than 2
 megohm)?
Yes
Yes
Clear out foreign matter
, open the valves
Check if the system is blocked, 
if the valves are open?
Yes
Check if the control 
valve of system is in normal condition.
 If the oil-balancing valve works normally, 
if the 
control terminals are well inserted, 
etc. If they 
are normal, please see the 
next step;
Yes
If there 
are other faults? Such as compressor 
startup failure (PJ), IPM module protection (P
6), 
desynchronizing protection of 
compressor (P9
).
Yes
The compressor is damaged, 
please replace it.
 
(47)   “P6” driven IPM module protection for compressor 
Error display: ODU mainboard displays  . 
Applicable model: all models. 
Condition and method for fault judgement:View the error code displayed in dual-8 nixie tube of 
main control board of ODU, if the nixie tube displays P6, it means driven IPM module protection for 
compressor. 
Possible causes: 
1)  Poor contact of compressor UVW wires. 
2)  Incorrect connecting order of compressor UVW wires.