5.2 Allowable Length and Fall for Refrigerant Pipe In IDU and ODU 
Model 
Pipe dimension (mm) 
Max pipe length 
(m) 
Max height difference between 
indoor unit and outdoor unit (m) 
Gas pipe  Liquid pipe 
UMLD400W/A-M(P) 
Ф25.4  Ф12.7  50  30 
UML500H/A-M(P) 
Ф34.9  Ф15.9  50  30 
UML600H/A-M(P) 
Ф34.9  Ф15.9  50  30 
5.3 Design of Oil Loop 
5.3.1 Purpose of Setting Oil Loop 
If big fall exist in the pipe, in order to prevent the problem that the refrigeration oil can’t return to the 
compressor effectively, oil loop must be set in the vertical pipeline. 
5.3.2 Principle of setting Oil Loop 
When there’s a difference between IDU and ODU, for the vertical gas pipe, an oil loop shall be 
installed every 10m from the bottom up. 
Oil loop shall adopt two U-shaped loops or one O-shaped loop, the height is 3
~
5 times the size of 
pipe diameter. 
5.3.3 Lnstallation Notices for Oil Loop 
For the vertical gas pipe, an oil loop shall be installed every 10m from the bottom up, meanwhile, the 
lowest/highest point of the vertical pipe shall be set with oil loop and check loop. 
5.3.4 Manufacture Requirement for Oil Loop and Check Loop 
Setting and manufacture method of oil loop is as follows: 
(1)  Set the oil loop as U-shape or O-shape; 
(2)  If ODU is below IDU, it’s needless to set oil loop at the lowest/highest point of the vertical pipe; 
if ODU is above IDU, then oil loop and check loop must be set separately at the lowest/highest 
point; 
(3)  Manufacture size of oil loop is as follows: