Troubleshooting: 
Yes
No
No
“
d5”midst pipe 
temperature sensor 
error
Is the terminal between 
mainboard and ambient temperature 
sensor loose or any foreign objects 
inside the terminal?
If it is loosened or there are 
foreign objects, retighten it 
after treatment
.
Check if the temperature 
sensor is abnormal
Yes
Replace temperature 
sensor
Check if the circuit is 
abnormal
Yes
Replace the main 
control board
 
 
(22)   “d6” Outlet pipe temperature sensor error 
Error display: IDU displays  . 
Error judgment condition and method: 
Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge 
the range of AD value. If the sampling AD value exceeds upper limit and lower limit in 5 seconds 
continuously, report the error. 
Possible reason: 
1)  Poor contact between outlet pipe temperature sensor and terminal in mainboard interface. 
2)  Outlet pipe temperature sensor is abnormal. 
3)  Detecting circuit is abnormal. 
(23)   “d9” Jumper cap error 
Error display: IDU displays  . 
Error judgment condition and method: 
Possible reason
: 
If jumper cap model doesn’t match with mainboard, report the error: 
1)  Jumper cap is not installed. 
2)  Jumper cap model is wrong. 
3)  Detecting circuit is abnormal.