GREE              Duct type Ducted Type Split Air-Conditioner Units 
108 
Troubleshooting: 
“P8” overheating 
protection for driven IPM 
of compressor
Check if the 
overheating protection for driven
 IPM of compressor occurs once the unit 
is energized?
Driven board of compressor is 
faulted
No
Replace the driven board of 
compressor
Yes
Check if the screw are firmly 
fixed, if the IPM module has been 
applied with radiating pasted
No
 
(50)   “P9” desynchronizing protection for inverter compressor 
Error display:ODU mainboard displays  . 
Applicable model: all models. 
Condition and method for fault judgement:View the error code displayed in dual-8 nixie tube of 
main control board of ODU, if the nixie tube displays P9, it means desynchronizing protection for inverter 
compressor. 
Possible causes: 
1)  Driven board of compressor is faulted. 
2)  Compresor is damaged.