GREE              Duct type Ducted Type Split Air-Conditioner Units 
107 
3)  Compresso is damaged. 
4)  The system is blocked. 
5)  IPM module of compressor driven board is damaged. 
(48)   “P7” malfunction of driven temperature sensor for compressor 
Error display: ODU mainboard displays  . 
Applicable model: all models. 
Condition and method for fault judgement:View the error code displayed in dual-8 nixie tube of 
main control board of ODU, if the nixie tube displays P7, it means malfunction of driven temperature 
sensor of compressor. 
Possible cause: 
1)  Driven board of compressor is faulted. 
Troubleshooting: 
“P7
” malfunction of driven 
tempberature sensor of compressor
Try to cut off the
 power for 3 times
, and then
 re-energize the unit
Compressor driven 
board is faulted
No
Replace the compressor 
driven board
Yes
 
(49)   “P8” overheating protection for driven IPM of compressor 
Error display: ODU mainboard displays  . 
Applicable model: all models. 
Condition and method for fault judgement:View the error code displayed in dual-8 nixie tube of 
main control board of ODU, if the nixie tube displays P8, it means overheating protection for driven IPM 
of compressor. 
Possible cause: 
1)  Screws for IPM module has not been firmly fixed. 
2)  No radiating paste in the IPM module, uneven application of radiating paste or the radiating 
paste is dry. 
3)  The driven board od compressor is faulted.