GREE              Duct type Ducted Type Split Air-Conditioner Units 
78 
01:Set master unit
02:Allocate addresses
03:Confirm the quantity of ODU
04:Confirm the quantity of IDU
07:Detect indoor components
06:Detect outdoor components
05:Detect ODU’s internal communication
08:Confirm preheated compressor
09:Confirm status of valve of ODU
10:Debugging completed status
 
 
1.4.4 Debugging Process 
Debugging procedure for test run, display instruction for indicator on main board of outdoor unit and 
operation method are as below: 
Description of each stage of debugging progress 
Instruction for Code and Operating Method 
Progress 
Display code 
Display 
Start  A0 
Always 
No debugged yeat. Press “SW3” button consecutively in the master 
module for over 5s to enter auto debugging. 
01_Master unit 
setting 
01/CC 
Display 
repeatedly 
The system has no master unit. 
Debugging can’t be continued, all buttons are invalid, disconnect 
the power to reset the correct “SA6” DIP. 
01/CF 
Display 
repeatedly 
The system has two or more master units. 
Debugging can’t be continued, all buttons are invalid, disconnect 
the power to reset the correct “SA6” DIP. 
01/oC 
Display 
repeatedly 
The system has only one master unit. 
After displaying once circularly, the system will enter the next step 
automatically.