5 Installation
5.1 Basic installation requirements
Ø The wall on which the inverter is mounted must be sturdy and can withstand the
weight of the inverter for a long time (refer to the specifications in Section 17 for the
weight of the inverter);
Ø The installation location should be suitable for the dimensions of the inverter;
Ø Do not install the inverter in areas with flammable or thermolabile materials;
Ø Install the inverter in an appropriate place for the user's ease to view and operate on
the display;
Ø The inverter is protected to IP66 and can be installed indoors and outdoors;
Ø The mounting location cannot be exposed to direct sunlight, which may cause
overheating. As a result, the inverter will reduce its power output;
Ø Keep the relative humidity at 0 to 90%;
Ø Keep the ambient temperature at -25°C to +60°C;
Ø Install the inverter vertically or at a maximum back tilt of 15 degrees. Do not install
the inverter at a front tilt, horizontally, or upside down.
Ø For the optimal operation of the equipment and the convenience of operation,
please reserve enough clearances around the inverter. The minimum clearances are listed
below:
Direction
Minimum clearance (mm)
Top
500
Bottom
500
Both sides
300
Front
300
Fig 5.1 Installation diagram
Ø Do not install the inverter near the television antenna or any other antennas and
antenna cables;
Ø Do not install the inverter in the living area;
Ø The mounting location must be inaccessible to children;
Ø Protect the inverter against direct sunlight and rain by installing a shelter or an
awning.
Fig 5.3 Clearance requirements for multiple inverters
Fig 5.2 Clearance requirements for a single inverter