46
45
Communication
fault;pairing time
too long
1.Re-pair the device.
2.If the error message persists, please contact
Growatt support.
1.Check grid frequency and restart the inverter.
2.If the error message persists, please contact
Growatt support.
1.Check whether the N line at the inverter side with
PV negative grounding is short circuited to the
ground wire, and whether the output side is isolated
with a transformer.
2.If error message still exisits,contact Manufacturer
1.After shutdown, check the connection of the CT or
the meter.
2.If the error message persists, please contact
Growatt support.
1.Restart the inverter.
2.If the error message persists, please contact
Growatt support.
Output voltage DC
component
overhigh
1.Restart the inverter.
2.If the error message persists, please contact
Growatt support.
Output current DC
component
overhigh
1.Restart the inverter.
2.If the error message persists, please contact
Growatt support.
Output current
unbalanced
1.After shutdown, check if the output current is
unbalanced.
2.If the error message still exists, contact
manufacturer.
1.Restart the inverter.
2.If the error message persists, please contact
Growatt support.
1.Restart the inverter.
2.If the error message persists, please contact
Growatt support.
Initialization mode
abnormal
1.Reset the mode.
2.If the error message persists, please contact
Growatt support.
1.Restart the inverter.
2.If the error message persists, please contact
Growatt support.
1.After shutdown, check the temperature. If it is
within the permissible range, restart the inverter.
2.If the error message still exists, contact the
manufacturer.
1.Restart the inverter.
2.If the error message persists, please contact
Growatt support.
Communication
board and control
panel sampling
battery voltage is
inconsistent
1.Restart the inverter.
2.If the error message persists, please contact
Growatt support.
Internal
communication
failure
1.After shutdown, check the wiring of the
communication board
2. If the error message still exists, contact
manufacturer
Temperature sensor
connection is
abnormal
1.After shutdown, check if the temperature sampling
module is properly connected.
2.If the error message still exists, contact
manufacturer
1.Restart the inverter.
2.If the error message persists, please contact
Growatt support.
1.Restart the inverter
2.If the error message persists, please contact
Growatt support.
Internal power test
failed (PV power
low)
1.Restart the inverter.
2.If the error message persists, please contact
Growatt support.
Over current
protected by
software
1.Restart the inverter.
2.If the error message persists, please contact
Growatt support.
System
communication
protocol mismatch
1.Restart the inverter.
2.If the error message persists, please contact
Growatt support.
DSP and COM
firmware version
mismatch
1.Check the firmware version.
2.If the error message persists, please contact
Growatt support.
DSP software
version and
hardware version
mismatch
1.Check the firmware version.
2.If the error message persists, please contact
Growatt support.
1.After shutdown,check the leakage current module.
2.If the error message still exists, contact
manufacturer.
1.Restart the inverter.
2.If the error message persists, please contact
Growatt support.
AC Volt/GFCI/ISO
sampling
inconsistent
1.Restart the inverter.
2.If the error message persists, please contact
Growatt support.