21
43
Battery equalization
Battery equalization enable
Battery equalization disable(default)
If Flooded or User-Defined is selected in program 05, this program can
be set up.
44
Battery equalization
voltage
Default 58.4V, 48.0V~58.4V Settable
45
Battery equalized time
Default 60min, 5min~900min
Settable
46
Battery equalized timeout
Default 120min, 5min~900min
Settable
47
Equalization interval
Default 30days, 1 days~90 days
Settable
48
Equalization activated
immediately
Equalization activated immediately
on
Equalization activated immediately
off(default)
If equalization function is enabled in program 43, this program can be setup.
If “On” is selected in this program, it’s to activate battery equalization
immediately and LCD main page will shows “ ”. If “Off” is selected, it will
cancel equalization function until next activated equalization time arrives
based on program 47setting. At this time, “ ” will not be shown in LCD
main page.
49
Utility charging time
0000(default)
Allow utility to charge the
battery all day run.
The time allows utility to charge the battery.
Use 4 digits to represent the time period, the
upper two digits represent the time when
utility start to charge the battery, setting
range from 00 to 23, and the lower two
digits represent the time when utility end to
charge the battery, setting range from 00 to
23.
(eg: 2320 represents the time allows utility
to charge the battery is from 23:00 to the
next day 20:59, and the utility charging is
prohibited outside of this period)
50
AC output time
0000(default)
Allow inverter to power the
load all day run.
The time allows inverter to power the load.
Use 4 digits to represent the time period, the
upper two digits represent the time when
inverter start to power the load, setting
range from 00 to 23, and the lower two
digits represent the time when inverter end
to power the load, setting range from 00 to
23.
(eg: 2320 represents the time allows inverter
to power the load is from 23:00 to the next
day 20:59, and the inverter AC output power
is prohibited outside of this period)