LCD Setting
After pressing and holding ENTER button for 3 seconds, the unit will enter setting mode. Press “UP” or “DOWN”
button to select setting programs. Then press “ENTER” button to confirm the selection or ESC button to exit.
Output source priority: To
configure load power
source priority
Solar energy provides power to the loads as first priority.
If solar energy is not sufficient to power all connected loads, battery
energy will supply power the loads at the same time.
Utility provides power to the loads only when any one condition happens:
-
Solar energy is not available
-
Battery voltage drops to either low-level warning voltage or the setting
point in program 12.
Utility will provide power to the loads as first priority.
Solar and battery energy will provide power to the loads only when
utility power is not available.
Solar energy provides power to the loads as first priority.
If solar energy is not sufficient to power all connected loads, battery will
supply power to the loads at the same time.
Utility provides power to the loads only when battery voltage drops to
either low-level warning voltage or the setting point in program 12.
Solar energy provides power to the loads as first priority.
If solar energy is not sufficient to power all connected loads, solar and
utility will power loads at the same time.
Battery provides power to the loads only when solar energy is not
sufficient and there is no utility.
Maximum charging current:
set total charging current for
solar and utility chargers.
(Max. charging current =
utility charging current +
solar charging current)
Default 60A, 10A~100A Settable
(If LI is selected in Program 5, this program can’t be set up)
Appliance (default)
If selected, acceptable AC input voltage range will be within 90~280VAC
UPS
If selected, acceptable AC input voltage range will be within 170~280VAC
Generator(Only diesel generators allowed)
If selected, acceptable AC input voltage range will be within 90~280VAC.
Note: When connecting generator, the generator should be no less than
10KVA(no less than 20KVA for three phase parallel system), and the
inverters should be no more than 2 units in one phase.