7.4 Establish connection to the Web server
The CIM 500 module can be configured using the built-in Web
server. To establish a connection from a PC to CIM 500 the
following steps are required:
Connect the PC and the CIM 500 module using an Ethernet
cable.
Configure the PC Ethernet port to the same subnetwork as the
CIM 500, e.g. 192.168.1.101, and the subnet mask to
255.255.255.0. See section A.1 How to configure an IP
address on your PC on page 90.
Open a standard Internet browser and type 192.168.1.100 in
the URL field.
Log in to the Web server using:
Fig. 17 CIM 500 connected to PC via Ethernet cable
For further information how to use the Web server, see section
A.2 Web server configuration on page 90.
7.5 Status LEDs
The CIM 500 Ethernet module has two Status LEDs, (LED1 and
LED2).
See fig. 15.
Red/green status LED (LED1) for Ethernet communication
Red/green status LED (LED2) for internal communication
between the CIM 500 and the Grundfos product.
LED1
LED2
7.6 DATA and LINK LEDs
The CIM 500 Ethernet module has two connectivity LEDs related
to each RJ45 connector. See fig. 15.
DATA1 and DATA2
These yellow LEDs indicate data traffic activity.
LINK1 and LINK2
These green LEDs shows whether the ethernet cable is properly
connected.
User Default: admin.
Password Default: Grundfos
Note
User and password may have been changed from
their factory default values.
TM05 6436 4712
Note
Both ETH1 and ETH2 can be used to establish a
connection to the Web server.
Note
The web server can be accessed while the selected
Industrial Ethernet protocol is active.
Status Description
Off
No Modbus TCP communication or
switched off.
Flashing green Modbus TCP communication active.
Permanently red
CIM 500 module configuration fault. See
section 16.3.1 LED status.
Permanently red and
green
Error in firmware download. See section
16.3.1 LED status.
Flashing red and
green
Resetting to factory default.
After 20 seconds the CIM 500 will
restart.
Status Description
Off The CIM 500 is switched off.
Flashing red
No internal communication between the
CIM 500 and the Grundfos product.
Permanently red
The CIM 500 does not support the
Grundfos product connected.
Permanently green
Internal communication between the
CIM 500 and the Grundfos product is
OK.
Permanently red and
green
Memory fault.
Note
During startup, there is a delay of up to 5 seconds
before LED1 and LED2 status is updated.
Status Description
Yellow off No data communication on RJ45 connector.
Yellow
flashing
Data communication ongoing on RJ45 connector.
Steady
yellow
Heavy network traffic on RJ45 connector.
Status Description
Green off No Ethernet Link on RJ45 connector
Green on Ethernet Link on RJ45 connector is OK