EasyManua.ls Logo

Grundfos CIM 250 - Event Log Register Block

Grundfos CIM 250
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
English (GB)
48
9.18 Event log register block
The event log contains the latest 50 event entries. Each entry
consists of seven registers, containing information about the
event.
Address Register name Scale Description
06001 NoOfEventsInLog Unscaled Number of events in the event log.
06002 EventIDLog1 Unscaled Event ID for logged event No 1.
06003 EventCodeLog1 enum Event code for logged event No 1.
06004 EventSourceLog1 enum
Event source for logged event No 1.
0 = System
1 = CU 36X
2 = IO 351B
3 = IO 111, pump
4 = MP 204, pump
5 = Analog input
6 = Pump
7 = Add-on CIM module
8 = Battery/UPS
9 = Mixer
10 = Analog input, level sensor
11 = Analog input, flow sensor
12 = Analog input, power sensor
13 = Analog input, user-defined sensor
14 = CUE (variable-frequency drive).
06005 EventDeviceNo Unscaled
Device number related to the event or its recognition.
0 = No related number
1 = Value of related number, pump 1
2 = Value of related number, pump 2
3 = Value of related number, pump 3
4 = Value of related number, pump 4
5 = Value of related number, pump 5
6 = Value of related number, pump 6.
06006 EventTypeAndConditionLog1 enum
Event type and condition of logged event No 1.
0 = -
1 = Alarm condition appears
2 = Alarm condition disappears
3 = Warning condition appears
4 = Warning condition disappears.
06007 EventTimeStampLog1HI
1 second Seconds since midnight January 1st 1970 (UNIX time).
06008 EventTimeStampLog1LO
06009-06344 Event log 2…49 - -
06345 EventIDLog50 Unscaled Event ID for logged event No 50.
06346 EventCodeLog50 enum Event code for logged event No 50.
06347 EventSourceLog50 enum Event source for logged event No 50.
06348 EventDeviceNo Unscaled Device number related to the event or its recognition.
06349 EventTypeAndConditionLog50 enum Event type and condition of logged event No 50.
06350 EventTimeStampLog50HI
1 second Seconds since midnight January 1st 1970 (UNIX time).
06351 EventTimeStampLog50LO