44
9.13 Pump 6 register block
All register values are read-only, and 0xFFFF indicates that the
data value is not available.
Unless otherwise stated, the data type used for counters and
scaled values is always an unsigned integer.
Address Register name Scale Description
00651
Pump6Status
Bit 0: Presence
Bool
Presence of pump.
0 = Not present
1 = Present.
Pump6Status
Bit 1: Running
Bool
Running state of pump.
0 = Not running
1 = Running.
Pump6Status
Bit 2: MonitoringFault
Bool
Fault state of pump monitoring devices.
0 = No fault
1 = Fault in auxiliary equipment or sensors.
Pump6Status
Bit 3: Warning
Bool
Warning state of pump.
0 = No warning
1 = Warning.
Pump6Status
Bit 4: Alarm
Bool
Alarm state of pump.
0 = No alarm
1 = Alarm.
Pump6Status
Bit 5: IO111Present
Bool
Presence of auxiliary equipment IO 111.
0 = Not present
1 = Present.
Pump6Status
Bit 6: IO111Fault
Bool
Fault state of auxiliary equipment IO 111.
0 = No fault
1 = Fault.
Pump6Status
Bit 7: MP204Present
Bool
Presence of auxiliary equipment MP 204.
0 = Not present
1 = Present.
Pump6Status
Bit 8: MP204Fault
Bool
Fault state of auxiliary equipment MP 204.
0 = No fault
1 = Fault.
Pump6Status
Bit 9: CUEPresent
Bool
Presence of auxiliary equipment CUE.
0 = Not present
1 = Present.
Pump6Status
Bit 10: CUEFault
Bool
Fault state of auxiliary equipment CUE.
0 = No fault
1 = Fault.
Pump6Status
Bit 11: PumpDisabled
Bool
Enabled/disabled state of pump.
0 = Enabled
1 = Disabled (e.g. for temporary maintenance).
00652 Pump6ControlSource enum
Control source of pump.
0 = Auto
1 = Switch
2 = Display
3 = Remote-controlled by bus.
00653 Pump6ConnectionType enum
Pump connection type.
0 = The pump is controlled from the CU 36X output relay.
1 = The pump is controlled from the IO 351B output relay.
2 = The pump is controlled from the CU 36X and VFD.
3 = The pump is controlled from the IO 351B and VFD.
00654 Pump6OperatingTimeHI
1 minute Total operating time.
00655 Pump6OperatingTimeLO
00656 Pump6TimeToServiceHI
1 minute Time to next service.
00657 Pump6TimeToServiceLO
00658 Pump6OperatingTimeYesterday 1 minute Operating time yesterday.
00659 Pump6OperatingTimeToday 1 minute Operating time today.
00660 Pump6LatestOperatingTime 1 second Operating time last time it was operated.
00661 Pump6StartCounterHI
Unscaled Total number of pump starts.
00662 Pump6StartCounterLO
00663 Pump6StartCounterYesterday Unscaled Total number of pump starts yesterday.
00664 Pump6StartCounterToday Unscaled Total number of pump starts today.
00665 Pump6StartsPerHour Unscaled Number of pump starts within the last hour.
00666 Pump6Flow 0.1 litre/s Calculated average or measured pump flow.
00667 Pump6LatestFlow 0.1 litre/s Latest calculated/measured flow (capacity).