00222 FloatSwitch4Function enum
Function of the float switch.
0 = Not used
1 = Dry running
2 = -
3 = Stop of all pumps
4 = Stop
5 = Stop of first pump
6 = Stop of second pump
11 = Start/stop
12 = Start of first pump/stop
13 = Start
14 = Start of first pump
15 = Start of second pump
20 = Start of all pumps
21 = Alarm level
23 = High level.
00223 FloatSwitch5Function enum
Function of the float switch.
0 = Not used
1 = Dry running
2 = -
3 = Stop of all pumps
4 = Stop
5 = Stop of first pump
6 = Stop of second pump
11 = Start/stop
12 = Start of first pump/stop
13 = Start
14 = Start of first pump
15 = Start of second pump
20 = Start of all pumps
21 = Alarm level
23 = High level.
00224
PitSensors
Bits 0:
UltrasonicLevelControlSensor
Bool
Presence of ultrasonic level control sensor.
0 = Not present
1 = Present.
PitSensors
Bits 1: PressureSensor
Bool
Presence of pressure sensor.
0 = Not present
1 = Present.
PitSensors
Bits 2: FloatSwitches
Bool
Presence of float switches.
0 = Not present
1 = Present.
PitSensors
Bit 3: FlowSensor
Bool
Presence of flow sensor.
0 = Not present
1 = Present.
PitSensors
Bit 4: Power/EnergySensor
Bool
Presence of power or energy sensor.
0 = Not present
1 = Present.
PitSensors
Bit 5: UserDefinedSensor1
Bool
Presence of user-defined sensor, analog input 1.
0 = Not present
1 = Present.
PitSensors
Bit 6: UserDefinedSensor2
Bool
Presence of user-defined sensor, analog input 2.
0 = Not present
1 = Present.
PitSensors
Bit 7: UserDefinedSensor3
Bool
Presence of user-defined sensor, analog input 3.
0 = Not present
1 = Present.
00225 DayCounterZeroTime enum
Zero time for today and yesterday counters.
Range: 0-23 hours.
00226 InterlockTimeout 1 second
Actual interlock timeout value in minutes.
A new value can be set in the SetInterlockTimeout (register 00111).
00227 InterlockRemainTime 1 second Remaining interlock time.
00228 RealTimeClockHI
1 second
The real-time clock in the CU 361 in seconds since midnight January 1st
1970 (UNIX time). See section 11.11 Real-time clock.
00229 RealTimeClockLO
00230 RtcSecond 1 second Second of the minute [0; 59]. See section 11.11 Real-time clock.
00231 RtcMinute 1 minute Minute of the hour [0; 59]. See section 11.11 Real-time clock.
00232 RtcHour 1 hour Hour of the day [0; 23]. See section 11.11 Real-time clock.
00233 RtcDay 1 day Day of the month [1; 31]. See section 11.11 Real-time clock.
00234 RtcMonth 1 month Month of the year [1; 12]. See section 11.11 Real-time clock
.