Pump alarms 4 (registers 00441 (pump 1), 00491 (pump 2), 00541 (pump 3), 00591 (pump 4), 00641 (pump 5), 00691 (pump 6))
Pump warnings 4 (registers 00442 (pump 1), 00492 (pump 2), 00542 (pump 3), 00592 (pump 4), 00642 (pump 5), 00692 (pump 6))
Leakage current PumpAlarms/Warnings4.0 1 CUE, pump No [1; 6]
Signal fault, temperature 3 sensor PumpAlarms/Warnings4.1 176 CUE, pump No [1; 6]
Signal fault, (feedback) sensor 1 PumpAlarms/Warnings4.2 89 CUE, pump No [1; 6]
Overcurrent PumpAlarms/Warnings4.3 49 CUE, pump No [1; 6]
Motor current protection activated PumpAlarms/Warnings4.4 55 CUE, pump No [1; 6]
Change bearings PumpAlarms/Warnings4.5 30 CUE, pump No [1; 6]
Lubricate bearings PumpAlarms/Warnings4.6 240 CUE, pump No [1; 6]
Automatic motor model recognition failed PumpAlarms/Warnings4.7 242 CUE, pump No [1; 6]
Communication fault, twin-head pump PumpAlarms/Warnings4.8 77 CUE, pump No [1; 6]
Signal fault, temperature 1 sensor PumpAlarms/Warnings4.9 91 CUE, pump No [1; 6]
Dry running PumpAlarms/Warnings4.10 57 CUE, pump No [1; 6]
VFD not ready PumpAlarms/Warnings4.11 213 IO 351B, pump No [1; 6]
Other PumpAlarms/Warnings4.12 16 CUE, pump No [1; 6]
Pump blocked PumpAlarms/Warnings4.13 51 CUE, pump No [1; 6]
Power sensor signal fault PumpAlarms/Warnings4.14 186 AI, pump No [1; 6]