EasyManua.ls Logo

Grundfos CIM 300 - Multistate Inputs; Multistate Outputs

Grundfos CIM 300
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.4 Multistate inputs
Binary objects that provide information from a Grundfos pump.
ID Object name R/W Description LC 2X1 LC 2X2
MI, 0 System Operating Mode R
0: Standby
1: Start-up delay
2: Pumping
3: Stop delay
4: Pumping max
5: Stopped
6: Foam draining
7: Daily emptying
8: Pump antiseizing
9: Manual control
10: Interlock control
11: Mains failure
12: Level sensor error
13: All pumps in alarm
14: All pumps out of operation
15: Service mode, alarms suppressed
MI, 1 CIM status R
1: OK
2: EEPROM fault
3: Memory fault
4: Unknown
MI, 2 System status R
STATUS_MAIN_STATUS reported by bits 0-2.
Possible values:
1: System OK
2: Warnings present
3: Alarms Present
4: Unknown
-
MI, 3 System control sensor type R
Reports the type of sensor controlling the system.
Possible values:
1: Analog level sensor
2: Float switch
3: Unknown
5.5 Multistate outputs
Objects that contain an enumeration value from the pump.
ID Object name R/W Description LC 2X1 LC 2X2
MO, 0 Control Pump 1 W
1: Auto
2: Forced start
3: Forced stop
MO, 1 Control Pump 2 W
1: Auto
2: Forced start
3: Forced stop
17
English (GB)

Related product manuals