ID Object name R/W Description LC 2X1 LC 2X2
BI, 30 UserDigitalInBlock, DI 13 R
0: Inactive
1: Active
-
BI, 31 UserDigitalInBlock, DI 14 R
0: Inactive
1: Active
-
BI, 32 UserDigitalInBlock, DI 15 R
0: Inactive
1: Active
-
BI, 33 UserDigitalInBlock, DI 16 R
0: Inactive
1: Active
-
BI, 34 Acknowledge ResetEventLogAlarm R
0: Not Acknowledged
1: Acknowledged
-
BI, 35 Control Status R
0: Auto control
1: Manual control
-
BI, 36 Motor1 max starts per hour limit exceeded R
0: No alarm
1: Alarm
BI, 37 Motor2 max starts per hour limit exceeded R
0: No alarm
1: Alarm
BI, 38 Running on battery back-up R
0: Inactive
1: Active
5.3 Binary outputs
Binary objects used for controlling a Grundfos pump.
ID Object name R/W Description LC 2X1 LC 2X2
BO, 0 Reset alarms W
0: No resetting
1: Resetting alarms
BO, 1 Reset EventLog W
0: No resetting
1: Resetting alarms
-