1.7 Specifications
General data Description Comments
Ambient humidity 30-95 % Relative, non-condensing.
Operating temperature -20 to +45 °C
Storage temperature -25 to +70 °C
GENIbus visual diagnostics LED2
The LED will be in one of these states:
Off, permanently green, flashing red, permanently red.
BACnet MS/TP Description Comments
BACnet connector Screw-type terminal 3 pins.
BACnet connection type RS-485
BACnet wire configuration Two-wire + ground Conductors: Plus, Minus and Ground.
Maximum cable length 1200 m Equals 4000 ft
Recommended cross-section of BACnet cable
0.20 - 0.25 mm
2
AWG24 or AWG23
MAC address 0-127 Set via rotary switches SW6 and SW7.
Line termination On or Off Set via DIP switches SW1 and SW2.
Supported transmission speeds [bit/s] 9600, 19200, 38400, 76800 Set via DIP switches SW4 and SW5.
Data bits 8 Fixed value
Stop bits 1 Fixed value
Parity None Fixed value
BACnet visual diagnostics LED1 Red and green status LED.
Maximum number of BACnet devices 32 Using repeaters, this number can be increased.
Grundfos BACnet vendor ID 227
BACnet segmentation support No
Character set support ANSI X3.4
Base definition for the widely used character code known as
ASCII.
BACnet device profile B-ASC BACnet Application-Specific controller
BACnet MS/TP master Yes CIM/CIU 300 and 500 are BACnet MS/TP master devices.
Manual slave address binding No
BACnet protocol revision
For hardware version R4: 4
For hardware version R8: 9
BACnet IP Description Comments
Application layer
DHCP, HTTP, Ping, FTP, SMTP, SNTP,
BACnet IP
Rotary switch in position 2.
Transport layer UDP
Internet layer Internet protocol V4 (IPv4)
Link layer ARP, media access control (Ethernet)
Ethernet cable CAT5, CAT5e or CAT6 Supports auto cable-crossover detecting (Auto-MDIX).
Maximum cable length 100 metres at 10/100 Mbit/s Corresponds to 328 feet.
Transmission speed 10 Mbit/s, 100 Mbit/s Auto-detected
Industrial Ethernet protocols PROFINET IO, BACnet IP etc. Selected with rotary switch.
BACnet protocol revision 9
CIM 300 and 500
Dimensions [w x h x d] [mm] 50 x 19 x 80
Power supply Supplied by the LC 2XX controller.
Connection to booster system 10-pin connection
Related information
2.2 CIM 300 BACnet module
2.3 Connecting to the BACnet network
2.4 Setting the BACnet transmission speed
2.7 Selecting the BACnet MAC address
2.8 Termination resistor
2.10 LEDs
2.10.1 LED1, BACnet MS/TP communication
3.2 Setting the Industrial Ethernet protocol